What the cold here does to a heat pump
Winter here is long and it gets genuinely cold. Heat runs eight months a year, October through May, and the overnight low averages 19°F across December, January and February. About 130 nights a year dip to freezing or below, over half the nights in that eight month stretch. A standard heat pump starts losing capacity below 40°F and often needs backup heat below about 35°F. By that measure, every single one of those 130 freezing nights here falls below both marks.
That does not mean the heat pump quits. About 5 nights a year reach 0°F or below, a small slice of the season, and newer cold-climate heat pumps are built for exactly this. To earn the ENERGY STAR Cold Climate label, a heat pump has to keep making real heat at 5°F, at least 1.75 units of heat per unit of electricity, and hold on to 70 percent of its rated capacity at that temperature. Field tests of these units in occupied homes back it up: backup heat only covered a small share of the load between 0°F and 35°F, and running on backup alone was rare even at 0°F. A furnace never has this problem. It is built for cold and does not lose capacity when the temperature drops.